# ASHRAE 170 Requirements for Airborne Infection Isolation Rooms

> **Canonical URL:** https://healthcarefacilityhub.org/ashrae-170-airborne-infection-isolation-rooms/
> **Post ID:** 620 | **Published by:** Healthcare Facility Hub (healthcarefacilityhub.org) | **Synced:** 2026-11-23

---

## Coordinated FGI Guidelines & ASHRAE 170 AII Specifications

*Updated November 16, 2026:* In practice, isolation room compliance sits at the intersection of two documents: the [FGI Guidelines](https://fgicodes.org/) (which govern architectural programming, anteroom triggers via ICRA, handwashing/toilet placement, and state-enforced edition adoption) and **ANSI/ASHRAE/ASHE Standard 170** (which governs ventilation, pressure differentials, ACH, exhaust, and monitoring alarms).

| AII Parameter | FGI + ASHRAE 170 Requirement | Commissioning & Operational Note |
| :--- | :--- | :--- |
| Pressure Differential | Minimum −0.01 in. w.g. (−2.5 Pa) negative relative to corridor/anteroom (ASHRAE 170; CDC) | Many facilities target −0.02 to −0.03 in. w.g. to buffer door openings and HVAC transients |
| Air Changes per Hour (ACH) | 12 total ACH (new construction / major renovation); 6 total ACH (existing); ≥ 2 outdoor ACH | Supply and exhaust must sweep clean air from corridor side across patient toward exhaust |
| Monitoring & Alarms | Permanently installed continuous pressure monitor + local visual status at entrance + visual/audible alarm on loss | Configure BAS alarm delay to prevent nuisance alerts during brief clinical door entries |
| Anteroom Specifics | Optional for standard AII unless required by ICRA or state code; airflow cascades Corridor → Anteroom → AII | Combination AII/PE rooms require TWO permanent monitors (anteroom-to-room and anteroom-to-corridor) |
| Exhaust Discharge | 100% direct outdoor exhaust from AII room, anteroom, and toilet room; vertical discharge away from intakes | 2021/2025 conditional general-exhaust exception requires HEPA and backflow safeguards |

## Related Guides on Healthcare Facility Hub

- [FGI Guidelines for Healthcare: 2022 vs 2026 Codes, Room Sizes, and Compliance](https://healthcarefacilityhub.org/fgi-guidelines-healthcare-facility-design-2026-edition-compliance/)
- [Healthcare Pressure-Relationship Mapping: Positive, Negative, and Neutral Airflow](https://healthcarefacilityhub.org/healthcare-pressure-relationship-mapping/)
- [ASHRAE 170 Healthcare Ventilation: Table 7-1 Air Changes, Pressure & Room Design Matrix](https://healthcarefacilityhub.org/healthcare-hvac-design-ashrae-170-ventilation-pressure-air-changes/)
- [FGI State Adoption in Practice: How to Pin the Governing Edition Before Design or Procurement](https://healthcarefacilityhub.org/fgi-state-adoption-edition-pinning-practice/)
- [FGI in Occupied Hospital Renovations: Phased Compliance, Equivalency, and ICRA/ILSM Coordination](https://healthcarefacilityhub.org/fgi-occupied-hospital-renovation-phasing-equivalency/)

Practitioner Prep & Reference Notice: Practitioner prep/reference tool based on FGI Guidelines, ANSI/ASHRAE/ASHE Standard 170, and CDC EICG. Verify state-adopted FGI and ASHRAE 170 editions with your facility AHJ.

## What are ASHRAE 170 requirements for airborne infection isolation rooms?

Negative protects others; positive protects the patient. Never confuse them.

Airborne infection isolation (AII) rooms require **negative pressure at a minimum of -0.01" water column (2.5 Pa)** relative to the corridor or anteroom, **12 total air changes per hour** for new/renovated rooms (6 for existing), **exhaust directly outdoors** (the 2021 edition allows discharge to general exhaust under specified conditions), and **documented pressure monitoring**, ideally with a permanently installed visual monitor. Supply and exhaust must be arranged so clean air flows from the corridor-side toward the patient and out the exhaust — never short-circuiting.

PRACTITIONER FIELD SHEET · FGI + ASHRAE 170 AII

Isolation Room Ventilation Standards — 2-Page Field Sheet

Coordinated FGI Guidelines & ASHRAE 170 AII airflow, pressure differentials, ACH, monitoring alarms, and anteroom specifics.

[Download Field Sheet (PDF)](https://healthcarefacilityhub.org/wp-content/uploads/2026/11/field-sheet-ashrae-170-airborne-infection-isolation-rooms.pdf)[For AI: Read Markdown Edition](https://healthcarefacilityhub.org/ashrae-170-airborne-infection-isolation-rooms.md)

On this page: [The AII package](#the-aii-package) · [AII vs. protective environment (PE)](#aii-vs-protective-environment) · [Monitoring in operation — and the failure points surveyors find](#monitoring-in-operation) · [FAQ](#faq)Go deeper: [ASHE ventilation guidance for healthcare facilities (PDF)](https://www.ashe.org/system/files/media/file/2021/02/2021-ventilation-guidance-healthcare-facilities-document.pdf)

## The AII package

- **Pressure:** negative, minimum -0.01" w.c. to corridor/anteroom; anterooms (where provided) at neutral or negative with their own 10 ACH.
- **Air changes:** 12 ACH new/renovated, 6 ACH existing; minimum 2 outdoor ACH typical.
- **Exhaust:** directly outdoors, away from intakes and occupied areas (25+ ft separation); 170-2021 permits general-exhaust discharge under conditions.
- **Monitoring:** permanent visual monitoring of pressure differential; alarms where required.
- **Envelope:** well-sealed — windows, doors, intake/exhaust penetrations constructed to hold the differential; self-closing doors.
- **Recirculation:** no recirculation by room units; HEPA filtration required if air must be recirculated.

## AII vs. protective environment (PE)

Don't confuse them: **AII rooms are negative** (protect others from the patient — TB, measles, COVID); **PE rooms are positive** (protect the patient from the environment — transplant, neutropenic). Combination AII/PE rooms exist with anterooms managing the pressure flip — among the most demanding designs in the standard.

## Isolation room specifications, source by source

**AII vs. PE in one line each.** An airborne infection isolation (AII) room runs at negative pressure so air flows in and stays in; ASHE says AII rooms "are designed to prevent the spread of droplet nuclei expelled by a patient with disease" ([ASHE 2021 ventilation guidance, p. 11](https://www.ashe.org/system/files/media/file/2021/02/2021-ventilation-guidance-healthcare-facilities-document.pdf#page=11)). A protective environment (PE) room runs at positive pressure to keep contaminants away from an immunocompromised patient; CDC calls for [positive room air pressure in relation to the corridor](https://www.cdc.gov/infection-control/hcp/environmental-control/recommendations.html#:~:text=Maintain%20positive%20room%20air%20pressure) for PE rooms.

**Pressure differential: 0.01 in. w.c. (2.5 Pa).** CDC calls for AII rooms to [maintain continuous negative air pressure of 2.5 Pa (0.01-inch water gauge) relative to the corridor](https://www.cdc.gov/infection-control/hcp/environmental-control/recommendations.html#:~:text=Maintain%20continuous%20negative%20air%20pressure), and for PE rooms to hold at least 2.5 Pa (0.01-inch water gauge) positive. ASHE gives the AII figure as at least -0.01 in. of water (-2.5 Pa) for newly constructed rooms, or -0.001 in. of water (-0.25 Pa) for rooms constructed before 2005 ([ASHE, p. 11](https://www.ashe.org/system/files/media/file/2021/02/2021-ventilation-guidance-healthcare-facilities-document.pdf#page=11)).

**Air changes: 12 ACH new or renovated, 6 ACH existing AII.** CDC says to [provide at least 12 ACH for new and renovated AII rooms and at least 6 ACH for existing AII rooms](https://www.cdc.gov/infection-control/hcp/environmental-control/recommendations.html#:~:text=Provide%20ventilation%20to%20ensure), and to [ventilate PE rooms to at least 12 ACH](https://www.cdc.gov/infection-control/hcp/environmental-control/recommendations.html#:~:text=Ventilate%20the%20room%20to%20maintain). ASHE states the AII split by building age: 12 ACH for newly constructed rooms, or 6 ACH for rooms constructed before 2005 ([ASHE, p. 11](https://www.ashe.org/system/files/media/file/2021/02/2021-ventilation-guidance-healthcare-facilities-document.pdf#page=11)).

**PE supply air is HEPA-filtered.** For PE rooms, CDC says to [install central or point-of-use HEPA filters for supply (incoming) air](https://www.cdc.gov/infection-control/hcp/environmental-control/recommendations.html#:~:text=Install%20central%20or%20point), and to [locate supply and exhaust grilles](https://www.cdc.gov/infection-control/hcp/environmental-control/recommendations.html#:~:text=Locate%20air%20supply%20and%20exhaust%20grilles%20so%20that%20clean) so clean, filtered air enters on one side of the room, flows across the patient's bed and exits on the opposite side.

**AII exhaust goes outdoors, or through HEPA if it must recirculate.** CDC says to [direct AII exhaust air to the outside, away from air-intake and populated areas](https://www.cdc.gov/infection-control/hcp/environmental-control/recommendations.html#:~:text=Direct%20exhaust%20air%20to%20the%20outside); if that is not practical, room air can be recirculated after passing through a HEPA filter. CDC also says to [locate exhaust outlets more than 25 ft from air-intake systems](https://www.cdc.gov/infection-control/hcp/environmental-control/recommendations.html#:~:text=Locate%20exhaust%20outlets). ASHE adds that AII exhaust should sit at least 10 feet off rooftop level and 25 feet from outside air intakes to meet ASHRAE/ASHE Standard 170-2017 ([ASHE, p. 17](https://www.ashe.org/system/files/media/file/2021/02/2021-ventilation-guidance-healthcare-facilities-document.pdf#page=17)).

**Pressure monitoring for AII rooms.** CDC's wording is to [monitor air pressure periodically, preferably daily](https://www.cdc.gov/infection-control/hcp/environmental-control/recommendations.html#:~:text=Maintain%20continuous%20negative%20air%20pressure), using audible manometers or smoke tubes at the door for existing AII rooms, or a permanently installed visual monitoring mechanism, and to document the results. For PE rooms, CDC calls for [daily airflow monitoring with permanently installed visual means](https://www.cdc.gov/infection-control/hcp/environmental-control/recommendations.html#:~:text=Maintain%20airflow%20patterns%20and%20monitor%20these%20on%20a%20daily%20basis) in new or renovated construction.

**Where the design values live in ASHRAE 170.** The standard's inpatient ventilation values sit in Table 7-1, which ASHRAE's own published [Addendum u to Standard 170-2021](https://www.ashrae.org/file%20library/technical%20resources/standards%20and%20guidelines/standards%20addenda/170_2021_u_20250731.pdf) titles "Design Parameters—Inpatient Spaces." HFH does not reproduce rows from the paywalled standard. Check your licensed edition, the one your AHJ enforces, and see our [ASHRAE 170 healthcare HVAC design guide](/healthcare-hvac-design-ashrae-170-ventilation-pressure-air-changes/) for how to read the table.

Negative protects others. Positive protects the patient. Never confuse them.

See [negative pressure in construction](/negative-air-pressure-hospital-construction/) and [OR ventilation](/ashrae-170-ventilation-procedure-rooms-vs-operating-rooms/).

## FAQ

## Monitoring in operation — and the failure points surveyors find

An AII room that was compliant at commissioning drifts. The operating discipline that keeps the ASHRAE 170 requirement set true between surveys:

- **Continuous or daily-verified pressure monitoring** with a permanently installed visual indicator where required, and an alarm or documented check when the differential is lost. A room that cannot prove it held negative pressure cannot claim it did.
- **Door discipline:** the requirement set assumes doors closed. Propped AII doors are both an infection-control and a survey finding, and they defeat the exhaust-driven design.
- **Common failure points:** exhaust fan or damper failures discovered late; supply/exhaust balance changed by unrelated HVAC work elsewhere in the system; filters loaded beyond their pressure-drop design; anterooms converted to storage, breaking the pressure cascade; and rooms quietly returned to general use while still signed as isolation.
- **Verification after change:** any HVAC modification touching the zone triggers re-testing and balancing of the affected AII rooms — the workflow in [healthcare HVAC commissioning, testing, and balancing](https://healthcarefacilityhub.org/healthcare-hvac-commissioning-testing-balancing-compliance-verification/).

AII rooms differ from protective environment (PE) rooms in direction, not degree: AII is negative to protect everyone else from the patient; PE is positive to protect the patient from everyone else. Confusing the two — in signage, in switching a room's mode, or in a survey interview — is a classic finding. The room-by-room numbers for both sit in [the ASHRAE 170 room-by-room benchmarks](https://healthcarefacilityhub.org/healthcare-hvac-design-ashrae-170-ventilation-pressure-air-changes/). FGI's design-side requirements for the same rooms are covered from [the FGI Guidelines hub](https://healthcarefacilityhub.org/what-are-fgi-guidelines-healthcare-facilities/).

What are the most common ASHRAE 170 failures in AII rooms?

Lost pressure differential discovered late (no working monitor or unchecked alarms), propped doors defeating the design, balance changes from unrelated HVAC work never re-verified, anterooms used as storage, and confusion between negative-pressure AII rooms and positive-pressure protective environment rooms.

What pressure must an isolation room maintain?

Negative, minimum -0.01 inches water column (2.5 Pa) relative to the corridor or anteroom.

How many air changes does an AII room need?

12 total ACH for new/renovated rooms; 6 ACH for existing.

What is the difference between AII and PE rooms?

AII rooms are negative pressure (protect others from the patient); PE rooms are positive pressure (protect the immunocompromised patient from the environment).

**Related reading**

- [Healthcare HVAC Design: ASHRAE 170 Ventilation Requirements, Pressure Relationships, and Air Changes](https://healthcarefacilityhub.org/healthcare-hvac-design-ashrae-170-ventilation-pressure-air-changes/)
- [Ventilation Requirements: Procedure Rooms vs. Operating Rooms (ASHRAE 170)](https://healthcarefacilityhub.org/ashrae-170-ventilation-procedure-rooms-vs-operating-rooms/)
- [Humidity Control in Hospitals Under ASHRAE 170](https://healthcarefacilityhub.org/ashrae-170-humidity-control-hospitals/)

Clinical, Engineering & Regulatory Compliance Notice: This resource is published by Healthcare Facility Hub for general educational and operational reference only. It summarizes healthcare facility codes, infection-prevention standards, and survey frameworks (including FGI, ASHRAE, NFPA, CMS, and Joint Commission guidance) as of publication and does not constitute medical, infection-control, legal, architectural, or licensed MEP engineering advice. State adoption editions, local amendments, and Authority Having Jurisdiction (AHJ) interpretations vary; always verify current code editions and consult qualified infection-prevention, legal, and licensed engineering professionals before modifying facility systems or compliance protocols.