# ASHRAE 170 Revision Tracking: Edition-to-Edition Changes (2017 to 2021 to 2025)

**Canonical URL:** https://healthcarefacilityhub.org/ashrae-170-edition-tracker/
**Parent Topic:** ASHRAE 170
**Field Sheet PDF:** https://healthcarefacilityhub.org/wp-content/uploads/2026/11/field-sheet-ashrae-170-revision-tracking.pdf

## Direct Answer

ANSI/ASHRAE/ASHE Standard 170-2025 is the current edition (incorporated into the 2026 FGI Codes), following ASHRAE 170-2021 (which absorbed 17 addenda to the 2017 edition). Key edition-to-edition shifts cover: (1) split Inpatient (Table 7-1), Outpatient (Tables 8-1/8-2), and Residential (Table 9-1) tables plus 2025 Behavioral/Mental Health and Class 2/3 imaging updates; (2) filtration MERV columns integrated directly into space tables with 2025 alternative filter-testing clarity; (3) unoccupied turndown formalized in 2021 and clarified for outpatient spaces in 2025; and (4) AII exhaust exceptions and mixed 170/62.1 outdoor-air rules.

## Core Reference Matrix

| Revision Area | 2017 Edition Baseline | 2021 Edition Shift (17 Addenda) | 2025 Edition Update (FGI 2026 Aligned) |
| :--- | :--- | :--- | :--- |
| Space Table Structure | Combined space tables; limited outpatient granularity | Split into Table 7-1 (Inpatient), Tables 8-1/8-2 (Outpatient), Table 9-1 (Residential) | Aligned with FGI 2026; updated Class 2/3 imaging, nuclear med & behavioral health (EmPATH) |
| Filtration Rules | Referenced in separate text/section rules | MERV minimums integrated as columns inside Tables 7-1, 8-1, 8-2, 9-1 | Added equivalent acceptable alternative filtration testing methodologies |
| Unoccupied Turndown | Limited / inconsistent project-by-project use | Formalized column/rules: turndown allowed if pressure relationship stays intact & full ACH restores pre-occupancy | Explicit clarifications for outpatient spaces (ambulatory/day-surgery setbacks) |
| Exhaust Allowances | Direct outdoor exhaust required for AII without general-exhaust tie-in | Added conditional exception allowing AII exhaust into general/central exhaust with safeguards | Maintained safeguards; clarified system-level outdoor air for mixed 170 + 62.1 systems |

## Project Edition Verification & Turndown Compliance Checklist

| Check | What to Verify Against State AHJ & FGI Adoption | Governing Source |
| :--- | :--- | :--- |
| 1. Enforced Edition | [ ] Confirm which FGI / ASHRAE 170 edition your state AHJ enforces (2013, 2017, 2021, or 2025) — never assume newest edition applies | State AHJ / FGI Adoption Map |
| 2. Table Lookup | [ ] Use Table 7-1 (Inpatient), 8-1 (Specialized Outpatient), or 8-2 (General Outpatient) matching the adopted edition | ASHRAE 170-2021 / 2025 |
| 3. Unoccupied Turndown | [ ] Verify BAS maintains continuous positive/negative pressure relationship during setback and restores full ACH before occupancy | ASHRAE 170-2021 / 2025 |
| 4. Exhaust Exceptions | [ ] Confirm direct outdoor exhaust for AII/decontam/bronchoscopy unless engineered backflow & filtration safeguards are AHJ-approved | ASHRAE 170-2021 / 2025 |

---

*Practitioner prep/reference tool based on ASHRAE / ASHE public summaries of Standard 170-2017, 170-2021, and 170-2025. Consult the licensed text of your state-adopted edition for exact numeric table parameters.*