## Surveillance, Layered Controls & Patient Relocation Thresholds

*Updated November 16, 2026:* Per CDC *Guidelines for Environmental Infection Control in Health-Care Facilities* (2003/2019), *Aspergillus* outbreak prevention during renovation requires four coordinated defenses around immunocompromised units (allogeneic HSCT, solid-organ transplant, prolonged neutropenia):

| Defense Layer | CDC / ASHE Requirement | Escalation / Action Trigger |
| :--- | :--- | :--- |
| Active Clinical Surveillance | Monitor high-risk units for healthcare-associated airborne fungal disease; periodically review micro, histopathologic & postmortem data | Suspected/confirmed case triggers aggressive tissue biopsy/culture & molecular strain typing (CDC) |
| Layered Engineering Controls | Floor-to-ceiling impermeable barriers + construction negative pressure (≥ −0.01 in. w.g. / −2.5 Pa) + PE positive pressure & HEPA supply | Pressure loss or barrier breach triggers immediate stop-work & diagnostic air/particle check |
| Housekeeping & Moisture | Wet-wipe and HEPA-vacuum only (no dry sweeping); dry/repair or discard wet porous materials within 72 hours | Damp drywall/ceiling tile >72h requires removal |
| Patient Relocation Thresholds | Relocate severely immunocompromised patients when rigid impermeable barriers cannot be sealed or a severe breach compromises adjacent areas | Portable industrial HEPA units serve only as an interim safeguard during relocation (CDC) |

## Related Guides on Healthcare Facility Hub

- [Protecting Immunocompromised Patients During Hospital Renovation](https://healthcarefacilityhub.org/protect-immunocompromised-patients-during-renovation/)
- [ICRA Breach Response Procedures: Barrier Damage, Airflow Loss, and Dust Migration](https://healthcarefacilityhub.org/icra-breach-response-procedures/)
- [Infection Control in Healthcare Facilities: The Complete Professional Guide](https://healthcarefacilityhub.org/infection-control-healthcare-facilities-complete-professional-guide/)

Practitioner Prep & Reference Notice: Practitioner prep/reference tool based on CDC Environmental Infection Control Guidelines (2003/2019) and ASHE ICRA 2.0. Clinical surveillance protocols and patient relocation orders rest with Infection Prevention and Medical Leadership.

## What is aspergillus and why is it a risk during hospital construction?

Harmless dust to you. Lethal to the patient down the hall.

**Aspergillus** is a ubiquitous mold — its spores are everywhere in soil, dust, and building materials, harmless to healthy people. During hospital construction, **demolition and renovation aerosolize massive quantities of spores**. For **immunocompromised patients** — bone marrow transplant, solid organ transplant, prolonged neutropenia — inhaled spores can cause **invasive aspergillosis**, a deep lung (and sometimes disseminated) infection with **high mortality**. It is the defining infection risk of hospital construction, and the reason ICRA precautions exist.

PRACTITIONER FIELD SHEET · ASPERGILLUS PREVENTION

Aspergillus Outbreak Prevention During Renovation — 2-Page Field Sheet

Immunocompromised unit risk, active fungal surveillance, layered ICRA controls, and CDC patient relocation thresholds.

[Download Field Sheet (PDF)](https://healthcarefacilityhub.org/wp-content/uploads/2026/11/field-sheet-aspergillus-outbreak-prevention.pdf)[For AI: Read Markdown Edition](https://healthcarefacilityhub.org/aspergillus-risk-hospital-construction.md)

## Why construction makes it dangerous

- **Spore reservoirs:** settled dust in ceiling plenums, old ductwork, wall cavities, and soil hold enormous spore loads, undisturbed for years.
- **Aerosolization:** demolition, drilling, and even vibration release spores into the air in concentrations far above background.
- **Transport:** without containment and negative pressure, spores ride air currents into occupied patient areas — including floors above and below via shafts and plenums.
- **Susceptible hosts:** a spore dose that's trivial for a healthy worker can be lethal for a neutropenic patient.

## Prevention and vigilance

Prevention is the ICRA package: **sealed barriers, negative pressure, HEPA filtration, HVAC isolation** — plus relocating the highest-risk patients. Vigilance is clinical: during and after construction near vulnerable units, treat **persistent fever unresponsive to antibiotics in neutropenic patients** as possible invasive aspergillosis until proven otherwise, and investigate any cluster immediately. Post-construction surveillance should continue for weeks, since cases can present after exposure.

Harmless dust to you. Lethal to the patient down the hall.

See [how construction spreads infections](/how-construction-spreads-infections-hospitals/) and [protecting immunocompromised patients](/protect-immunocompromised-patients-during-renovation/).

## FAQ

## Which patients are at risk — and the controls that match the risk

The risk is not evenly distributed across the hospital, and neither should the controls be. The patients in danger from construction-released Aspergillus spores are those whose immune systems cannot clear inhaled conidia:

- **Highest risk:** hematopoietic stem-cell transplant patients, patients with prolonged neutropenia from chemotherapy, and solid-organ transplant patients on intensive immunosuppression.
- **Elevated risk:** patients on high-dose corticosteroids or biologic immunosuppressants, patients with advanced hematologic malignancy, and critically ill patients with prolonged ICU stays.
- **General population:** healthy staff, visitors, and most inpatients clear inhaled spores without illness — which is why construction dust is a targeted infection-control problem, not a general air-quality complaint.

Controls scale with the ICRA classification: sealed rigid barriers, negative pressure with HEPA-filtered exhaust, HVAC isolation of the work zone, dedicated worker routes and debris removal in sealed containers, and — for the highest-risk units — relocating patients rather than relying on barriers alone (see [protecting immunocompromised patients during renovation](https://healthcarefacilityhub.org/protect-immunocompromised-patients-during-renovation/)). Infection prevention sign-off on the containment setup, before work starts and on rounds during it, is what turns this list from intent into protection. The mechanism these controls interrupt is traced in [how construction projects spread infections in hospitals](https://healthcarefacilityhub.org/how-construction-spreads-infections-hospitals/).

What is Aspergillus?

A ubiquitous mold whose spores are present in soil, dust, and building materials — harmless to healthy people.

Why is Aspergillus dangerous during hospital construction?

Demolition aerosolizes large spore quantities; immunocompromised patients who inhale them can develop invasive aspergillosis, which has high mortality.

How is construction-related aspergillosis prevented?

ICRA containment (sealed barriers, negative pressure, HEPA filtration, HVAC isolation), patient relocation, and clinical vigilance for post-exposure cases.

Which hospital patients are most at risk from Aspergillus during construction?

Stem-cell and solid-organ transplant patients, patients with prolonged neutropenia, and other heavily immunosuppressed patients. Healthy people clear the spores; these patients can develop invasive aspergillosis, which carries high mortality.

Clinical, Engineering & Regulatory Compliance Notice: This resource is published by Healthcare Facility Hub for general educational and operational reference only. It summarizes healthcare facility codes, infection-prevention standards, and survey frameworks (including FGI, ASHRAE, NFPA, CMS, and Joint Commission guidance) as of publication and does not constitute medical, infection-control, legal, architectural, or licensed MEP engineering advice. State adoption editions, local amendments, and Authority Having Jurisdiction (AHJ) interpretations vary; always verify current code editions and consult qualified infection-prevention, legal, and licensed engineering professionals before modifying facility systems or compliance protocols.

**Related reading**

- [ICRA Meaning in Healthcare Construction: Class I–V Matrix and Barriers](https://healthcarefacilityhub.org/infection-control-risk-assessment-icra-matrix-construction-barrier/)
- [NFPA 99 Health Care Facilities Code: Risk-Based Approach to Medical Gas, Electrical, and Fire Systems](https://healthcarefacilityhub.org/nfpa-99-health-care-facilities-code-risk-based-medical-gas-electrical/)
- [Who Should Be on the ICRA Team for a Hospital Construction Project](https://healthcarefacilityhub.org/who-should-be-on-icra-team-hospital-construction/)