# Healthcare Pressure-Relationship Mapping: Positive, Negative, and Neutral Airflow by Clinical Purpose

**Canonical URL:** https://healthcarefacilityhub.org/healthcare-pressure-relationship-mapping/
**Parent Topic:** ASHRAE 170
**Field Sheet PDF:** https://healthcarefacilityhub.org/wp-content/uploads/2026/11/field-sheet-healthcare-pressure-relationship-mapping.pdf

## Direct Answer

ASHRAE Standard 170 Table 7-1 and Tables 8-1/8-2 assign every clinical space a mandatory pressure relationship — Positive (+), Negative (-), or Neutral / No Requirement (NR) — based on contamination-control purpose. Positive rooms (ORs, Protective Environments, SPD Clean Workrooms, Sterile Storage) push air outward to protect sterile fields or immunocompromised patients; Negative rooms (AII, SPD Decontamination, Bronchoscopy, Soiled Workrooms) pull air inward and exhaust outdoors to contain pathogens, moisture, and vapors. Automated pressure-switching between positive and negative is prohibited.

## Core Reference Matrix

| Clinical Space (ASHRAE 170) | Pressure | Airflow Direction | Contamination-Control Purpose | Exhaust Rule |
| :--- | :--- | :--- | :--- | :--- |
| Operating Room (Class B & C) | Positive (+) | Room -> Corridor | Protects open sterile surgical field from corridor contaminants | Recirculation permitted w/ MERV/HEPA |
| Protective Environment (PE) | Positive (+) | Room -> Corridor/Anteroom | Protects severely immunocompromised patients from airborne spores | HEPA-filtered supply; no switching |
| Airborne Infection Isolation (AII) | Negative (-) | Corridor/Anteroom -> Room | Contains TB, measles, varicella & airborne infectious aerosols | 100% direct outdoor exhaust* |
| SPD Decontamination | Negative (-) | Clean/Corridor -> Decontam | Contains bioaerosols, steam & chemical vapors from instrument wash | 100% direct outdoor exhaust |
| SPD Clean Workroom & Sterile Storage | Positive (+) | Clean -> Decontam/Corridor | Protects cleaned instruments & sterile packaging integrity | Cascades toward Decontam |
| Bronchoscopy / Soiled Workroom / Autopsy | Negative (-) | Corridor -> Room | Contains infectious aerosols, odors & biohazardous particulates | 100% direct outdoor exhaust |
| General Patient Room / Exam / Corridor | Neutral (NR) | Balanced / No Requirement | Standard clinical occupancy without specialized containment | Per Table 7-1 / 8-2 |

## Pressure-Mapping & Commissioning Verification Checklist

| Verification Item | Field Check / Governing Rule | Owner |
| :--- | :--- | :--- |
| 1. No Pressure Switching | [ ] Confirm automated BAS controls cannot switch a room between Positive and Negative (prohibited by ASHRAE 170 due to failure risk) | Engineering / TAB |
| 2. Suite Cascade | [ ] Verify directional cascade in multi-room suites (e.g., SPD Sterile Storage (+) -> Clean Workroom (+) -> Decontamination (-)) | TAB / Facilities |
| 3. Permanent Monitors | [ ] Verify permanently installed visual differential pressure monitors on all AII and PE rooms | Facilities / Clinical |
| 4. Smoke / Tissue Test | [ ] Perform qualitative airflow direction check at door undercut alongside quantitative manometer reading during TAB & rounds | Engineering / IP |

---

*Practitioner prep/reference tool based on ANSI/ASHRAE/ASHE Standard 170 Table 7-1 & Tables 8-1/8-2. *2021/2025 exceptions permit AII exhaust tie-in only with AHJ-approved backflow/filtration safeguards. Verify state-adopted edition.*