Updated: November 16, 2026. Practitioner prep/reference material only — clinical thresholds, medication administration workflows, and code interpretations must be spot-checked by qualified clinical, pharmacy, and Authority Having Jurisdiction (AHJ) leadership before adoption.
1. The Clinical Paper Fallback Pack (48-Hour Unit Staging)
Per ONC SAFER Contingency Planning principles, generic or outdated paper forms introduce medication and transcription errors. Clinical, pharmacy, and Health Information Management (HIM) leaders should spot-check and seal each unit’s red or teal downtime binder with the following components:
| Kit Component | Staging Target (Practice) | Accountable Owner | Pre-Event Verification |
|---|---|---|---|
| Paper Order Sets & MAR Sheets | 48-hour census supply; layout mirroring current EHR screens (not legacy forms). | Nursing & Pharmacy | Confirm revision date matches current EHR formulary. |
| Patient-Tracking Board & Census Log | Wall dry-erase board + laminated census sheets (Room, Name, MRN, Acuity, Location). | Charge Nurse / HUC | Stock dry-erase markers, erasers, and clipboards. |
| Downtime Wristbands & Lab Labels | Pre-numbered downtime specimen labels + permanent fine-tip markers. | HIM / Admitting / Lab | Verify sequence blocks and printer-battery backup. |
| Unit-Specific Consent & Transfer Forms | Tailored packets for ED, ICU, Med-Surg, OR, and OB/Maternal Care. | HIM & Unit Manager | Keep 48-hour pack sealed with breakaway tamper tag. |
| Standalone Offline Downtime PC | Air-gapped, disk-imaged read-only workstation on local UPS (not network-dependent). | IT / Clinical Informatics | Verify local MAR sync schedule and UPS battery test. |
2. Unit Contact Tree and Redundant Hardware
To satisfy Joint Commission EM.12.02.01 and CMS 42 CFR 482.15(c) communication continuity, stage a laminated contact tree inside the front cover of every kit listing internal extensions, dedicated UHF/VHF radio channels, analog POTS numbers, and external utility/vendor/EMS contacts for HICS Command, Plant Operations, IT Downtime Lead, Pharmacy, Lab, and Security.
3. Facility Utility Shutoff Maps Checklist
During a combined utility and IT outage, nurses and engineers often need to isolate a leaking riser, confirm red-outlet power, or verify a medical gas zone valve without access to CAD servers or CMMS tablets. Include laminated copies of these four maps in both Plant Ops and unit binders:
| Utility System | Required Map / Directory Content | Physical Hardware in Kit |
|---|---|---|
| Electrical (NFPA 99 EES) | Panel schedule distinguishing Red (Critical/Life Safety) vs. White outlets; ATS locations; load-shed sequence. | Headlamp, area flashlight, spare batteries, breaker lockout tags. |
| Medical Gas (NFPA 99) | Zone valve box locations by wing/floor; bulk O2 & reserve manifold locations; clinical sign-off rule before shutoff. | Zone valve keys (if locked) + portable O2 cylinder regulator wrench. |
| Potable & Chilled Water | Main and riser isolation valves; sterile processing & dialysis feeds; backflow and Legionella flush points. | Valve tag directory, waterproof flashlight, spill absorbent. |
| HVAC & Pressure Zones | AHU-to-wing map showing AII/OR/Pharmacy positive/negative zones and manual damper/restart steps. | Portable manometer / tissue-test checklist + temporary door-seal tape. |
4. Quarterly Inspection and 24-Hour Restock Rule
- Quarterly Seal & Battery Audit: Inspect tamper tags, test UHF/VHF radios and flashlights, and verify paper MAR/order forms match current EHR builds.
- 24-Hour Post-Event Restock: Any kit opened during a drill or live outage must be restocked, reconciled with HIM/Pharmacy, and re-sealed within 24 hours of restoration.
- Full Command Playbook: Use this kit alongside the Joint Clinical and Facility Downtime Playbook for 0–15 min, 15–60 min, and 1–8+ hr command execution.
Related Guides on Healthcare Facility Hub
- Joint Clinical and Facility Downtime Playbook: Combined EHR, Communications, and Utility Outage Response
- How Healthcare Facility Managers Reduce Downtime Across Critical Systems
- Healthcare Facilities Prepare for Emergency Disruptions and Outages
- CMS Emergency Preparedness Rule Requirements for Hospitals