Direct Answer: Under ANSI/ASHRAE/ASHE Standard 170 (Inpatient Table 7-1 and Outpatient Tables 8-1/8-2), every clinical space is assigned a mandatory pressure relationship—Positive (+), Negative (−), or Neutral / No Requirement (NR)—based strictly on its contamination-control purpose. Positive rooms (Operating Rooms, Protective Environments, Sterile Processing clean workrooms and sterile storage) supply more air than they exhaust so clean air flows outward to protect patients or sterile supplies. Negative rooms (Airborne Infection Isolation, SPD decontamination, bronchoscopy, soiled workrooms) exhaust more air than they supply and discharge outdoors to contain pathogens, moisture, and chemical vapors. Automated controls that switch a room between positive and negative pressure are prohibited by ASHRAE 170.
The Three Pressure Classifications and Contamination-Control Logic
Pressure relationships in healthcare HVAC are directional containment tools, not comfort settings. When a door opens or air leaks across a wall penetration, air moves from higher pressure to lower pressure:
- Positive (+): Supply airflow exceeds exhaust airflow. Air moves outward into adjacent corridors or anterooms to keep airborne spores, dust, and unconditioned corridor air out of a sterile or immunocompromised zone.
- Negative (−): Exhaust airflow exceeds supply airflow. Air moves inward from adjacent spaces so infectious aerosols, biohazards, moisture, or chemical vapors cannot escape into clean clinical areas.
- Neutral / No Requirement (NR): ASHRAE 170 mandates no directional airflow across the doorway; standard clinical occupancy ventilation applies unless a facility ICRA specifies otherwise.
Room-by-Room Pressure-Relationship Map (ASHRAE 170 Table 7-1)
The table below maps core inpatient and support spaces from ANSI/ASHRAE/ASHE Standard 170 Table 7-1 to their contamination-control purpose and exhaust rules. Exact numeric ACH and filtration parameters depend on the edition of ASHRAE 170 and FGI Guidelines enforced by your state AHJ.
| Clinical Space | Pressure Relationship | Airflow Direction | Contamination-Control Purpose | Exhaust / Recirculation Rule |
|---|---|---|---|---|
| Operating Room (Class B & C Surgery) | Positive (+) | Room → Corridor | Protects open sterile surgical field from corridor particulates | Recirculation permitted via Table 7-1 filtration |
| Protective Environment (PE) | Positive (+) | Room → Corridor / Anteroom | Protects severely immunocompromised patients (e.g., HSCT) from fungal spores | HEPA-filtered supply; permanent visual monitor required |
| Airborne Infection Isolation (AII) | Negative (−) | Corridor / Anteroom → Room | Contains airborne infectious pathogens (TB, measles, varicella) | 100% direct outdoor exhaust (or qualifying 2021/2025 exception) |
| SPD Decontamination | Negative (−) | Clean / Corridor → Decontam | Contains bioaerosols, steam, and detergent vapors from instrument washing | 100% direct outdoor exhaust |
| SPD Clean Workroom & Sterile Storage | Positive (+) | Clean → Decontam / Corridor | Protects disinfected instruments and sterile packaging integrity | Cascades toward negative Decontamination |
| Bronchoscopy / Sputum Induction | Negative (−) | Corridor → Room | Contains aerosolized respiratory secretions during procedures | 100% direct outdoor exhaust |
| Soiled Workroom / Janitor Closet / Autopsy | Negative (−) | Corridor → Room | Contains odors, biohazards, and wet-cleaning aerosols | 100% direct outdoor exhaust |
| General Patient Room / Exam / Corridor | Neutral (NR) | Balanced / No Requirement | Standard clinical care without specialized isolation containment | Governed by ASHRAE 170 Table 7-1 / 8-2 |
Cascading Pressure Gradients in Multi-Room Suites
Single-room pressure checks fail when adjacent support rooms pull air the wrong way. In multi-room departments such as Sterile Processing (SPD), Pharmacy compounding, and Surgical Suites, pressure must cascade monotonically from the cleanest zone to the dirtiest zone—for example: Sterile Storage (+) → Clean Workroom (+) → Corridor (NR) → Decontamination (−).
No Automated Pressure-Switching & Permanent Monitoring Rules
- No Pressure Switching: ASHRAE Standard 170 prohibits using automated HVAC controls to switch a room’s mandatory pressure relationship between positive and negative (for example, flipping an AII room to PE mode via a BAS toggle) because control failures and human error create severe patient-safety hazards.
- Permanent Visual Monitors: Spaces with critical pressure boundaries—specifically AII and PE rooms—require permanently installed differential pressure monitoring mechanisms visible to clinical staff at the room entrance.
- Unoccupied Turndown Guardrail: Under ASHRAE 170-2021 and 170-2025, spaces eligible for unoccupied ACH turndown may only reduce airflow if the required positive or negative pressure relationship to adjacent spaces is continuously maintained.
Related Guides on Healthcare Facility Hub
- ASHRAE 170 Healthcare Ventilation: Table 7-1 Air Changes, Pressure & Room Design Matrix
- ASHRAE 170 Edition Tracker: Which Version Applies to Your Facility (2008–2025)
- Operating Room HVAC: Laminar Flow, Temperature Control, Humidity Ranges, and Particulate Filtration
- Isolation Room Ventilation Standards: FGI & ASHRAE 170 AII Requirements
Get the weekly brief
Surveys, water, plant and readiness — what we measured and what changed in facility operations, every week.